Heat pumps NF - Air to water, heating, and cooling

Model ACHP-H14/5R2HA-M

Range

A-thermal

Diploma nb.

25.04.012

Participant

Ningbo AUX ELECTRIC CO. LTD.

Brand

AUX

LwO Env

59 dB(A)

Pdesignh (W35)

14.50 kW

Qhe (W35)

6317.00 kWh

SCOPon (W35)

4.74

SCOP (W35)

4.73

ηs,h (W35)

186.00 %

Pdesignh (W55)

14.00 kW

Qhe (W55)

7563.00 kWh

SCOPon (W55)

3.84

SCOP (W55)

3.83

ηs,h (W55)

150.00 %

Ph

14.00 kW

Pe

2.92 kW

COP

4.80

Pe

0.00 kW

Ph

14.00 kW

Pe

4.38 kW

COP

3.20

PhA (W35)

12.83 kW

COP A (W35)

3.00

PhB (W35)

7.81 kW

COP B (W35)

4.52

PhC (W35)

5.02 kW

COP C (W35)

6.40

PhD (W35)

4.68 kW

COP D (W35)

10.00

TOL (W35)

-10.00 °C

PhE (W35)

11.46 kW

COP E (W35)

2.73

Tbiv (W35)

-7.00 °C

PhF (W35)

12.83 kW

COP F (W35)

3.00

LwO (W35)

59.00 dB(A)

PhA (W55)

12.38 kW

COP A (W55)

2.40

PhB (W55)

7.54 kW

COP B (W55)

3.66

PhC (W55)

4.85 kW

COP C (W55)

5.18

PhD (W55)

2.15 kW

COP D (W55)

6.58

TOL (W55)

-10.00 °C

PhE (W55)

10.50 kW

COP E (W55)

2.13

Tbiv (W55)

-7.00 °C

PhF (W55)

12.38 kW

COP F (W55)

2.40

LwO (W55)

59.00 dB(A)

Taux

0.68 %

Psbh

20.00 W

reference code

16119022000023

HP Detailed reference

ACHP-H14/5R2HA-M

Main Power Supply

400-3-50

Liquid Refrigerant

R290

Type

Monobloc

Location

Outdoor

Compressor system

Variable

Compressor Type

Twin Rotary