Variable refrigerant flow systems - Air cooled, reversible

Model RXYSQ12TY1

Range

RXYSQ-TY1

Diploma nb.

15.02.244

Participant

20

Brand

DAIKIN

Pc

33.50 kW

Pec

12.41 kW

EER

2.70

Ph

33.50 kW

Peh

8.19 kW

COP

4.09

Pdesignc

33.5000 kW

SEER

6.49

ηsc

256.60 %

Pc PL CondB

24.70 kW

EER PL CondB

4.30

Pc PL CondC

15.90 kW

EER PL CondC

7.90

Pc PL CondD

7.30 kW

EER PL CondD

13.60

Pdesignh

23.50 kW

SCOP

4.32

ηsh

169.80 %

Ph PL CondA

20.80 kW

COP PL CondA

2.40

Ph PL CondB

12.70 kW

COP PL CondB

4.30

Ph PL CondC

8.10 kW

COPC

6.30

Ph PL CondD

6.60 kW

COP PL CondD

6.70

TOL

-10.0000 °C

Ph PL CondE TOL

23.5000 kW

COP PL CondE TOL

2.2000

Tbiv

-10.00 °C

Ph PL CondF Tbiv

23.50 kW

COP PL CondF Tbiv

2.20

Psbc

46.00 W

Poffc

46.00 W

Ptoc

13.00 W

Pckc

0.00 W

Psbh

46.00 W

Poffh

46.00 W

Ptoh

59.00 W

Pckh

46.00 W

LwO env

76.00 dB(A)

LwO env in heating

76.00 dB(A)

CcpLRcontminc

2.9300

LRcontminc

0.4000

CcpLRcontminh

1.5400

LRcontminh

0.2400

IU Names

6x FXFQ50B

Mounting

cassette

Refrigerant

R410A

Main Power Supply

400-3-50

Cd

0.2500