Variable refrigerant flow systems - Air cooled, reversible

Model RV6-450DN/S1-C

Range

RV6

Diploma nb.

17.10.001

Participant

2354

Brand

RTEC

Pc

45.00 kW

Pec

20.09 kW

EER

2.24

Ph

45.00 kW

Peh

12.23 kW

COP

3.68

Pdesignc

45.0000 kW

SEER

6.24

ηsc

246.60 %

Pc PL CondB

33.15 kW

EER PL CondB

3.90

Pc PL CondC

21.31 kW

EER PL CondC

7.38

Pc PL CondD

9.47 kW

EER PL CondD

18.00

Pdesignh

23.50 kW

SCOP

4.84

ηsh

190.60 %

Ph PL CondA

20.71 kW

COP PL CondA

2.90

Ph PL CondB

12.65 kW

COP PL CondB

4.50

Ph PL CondC

8.13 kW

COPC

7.20

Ph PL CondD

6.21 kW

COP PL CondD

9.20

TOL

-10.0000 °C

Ph PL CondE TOL

23.5000 kW

COP PL CondE TOL

2.3000

Tbiv

-10.00 °C

Ph PL CondF Tbiv

23.50 kW

COP PL CondF Tbiv

2.30

Psbc

20.00 W

Poffc

20.00 W

Ptoc

40.00 W

Pckc

10.00 W

Psbh

25.00 W

Poffh

25.00 W

Ptoh

50.00 W

Pckh

50.00 W

LwO env

93.00 dB(A)

LwO env in heating

92.00 dB(A)

IU Names

2x GMV-ND71PHS/B3-T + 4x GMV-ND80PHS/B3-T

Mounting

ducted

Refrigerant

R410A

Main Power Supply

400-3-50

Cd

0.2500