Chillers & Heat pumps - Heat pump, air-to-water, split, reversible

Model EWYT064+064CZ(I+O)-A2

Range

EWYT-CZ

Diploma nb.

97.01.160

Participant

1249

Brand

DAIKIN

Lw

83.0 dB(A)

Pc

64.41 kW

EER

2.95

Apc Indoor

207.20 kPa

SEER

5.34

ηsc

211.0 %

Water Regulation

VW/VO

Ph

61.12 kW

COP

3.92

Aph Indoor

209.00 kPa

Ph

61.90 kW

COP

2.72

Aph Indoor

249.30 kPa

Pdesignh

48.88 kW

SCOP

4.01

ηsh

157.0 %

Water Regulation

VW/VO

Lw

83.0 dB(A)

SEPR

7.23

Water Regulation

VW/VO

Refrigerant

R32

Main Power Supply

400-3-50

Control of Pump Speed

Variable

Unit Capacity Control

Variable

Type

Scroll

Inverter

true

Number

2