Variable refrigerant flow systems - Air cooled, reversible
Pc
12.30 kW
Pec
3.73 kW
EER
3.30
Ph
14.00 kW
Peh
4.33 kW
COP
3.23
Pdesignc
12.3000 kW
SEER
6.62
ηsc
261.80 %
Qce
1123.31 kWh/annum
Pc PL CondB
9.06 kW
EER PL CondB
5.36
Pc PL CondC
5.83 kW
EER PL CondC
7.82
Pc PL CondD
5.19 kW
EER PL CondD
11.31
Pdesignh
8.30 kW
SCOP
3.94
ηsh
154.60 %
Ph PL CondA
7.34 kW
COP PL CondA
2.41
Ph PL CondB
4.47 kW
COP PL CondB
3.75
Ph PL CondC
3.36 kW
COPC
5.78
Ph PL CondD
4.14 kW
COP PL CondD
7.24
TOL
-10.0000 °C
Ph PL CondE TOL
8.3000 kW
COP PL CondE TOL
2.0700
Tbiv
-10.00 °C
Ph PL CondF Tbiv
8.30 kW
COP PL CondF Tbiv
2.07
Psbc
23.00 W
Poffc
23.00 W
Ptoc
5.00 W
Pckc
5.00 W
Psbh
23.00 W
Poffh
23.00 W
Ptoh
28.00 W
Pckh
5.00 W
LwO env
75.00 dB(A)
LwO env in heating
75.00 dB(A)
LwI1 duct in heating
62.0000 dB(A)
LwI2 duct in heating
64.0000 dB(A)
CcpLRcontminc
3.4300
LRcontminc
0.1000
CcpLRcontminh
2.2400
LRcontminh
0.1000
IU Names
3x Q4DN-2-XMi D28+1x Q4DN-2-XMi D45
Mounting
ducted
Refrigerant
R410A
Main Power Supply
230-1-50
Cd
0.2500