Variable refrigerant flow systems - Air cooled, reversible

Model PUHY-EP300YNW-A2

Range

Y-Series

Diploma nb.

15.10.006

Participant

44

Brand

MITSUBISHI ELECTRIC

Pc

33.50 kW

Pec

9.68 kW

EER

3.46

Ph

33.50 kW

Peh

8.27 kW

COP

4.05

Pdesignc

33.5000 kW

SEER

7.26

ηsc

287.40 %

Pc PL CondB

24.68 kW

EER PL CondB

5.12

Pc PL CondC

15.87 kW

EER PL CondC

8.85

Pc PL CondD

9.30 kW

EER PL CondD

14.53

Pdesignh

17.09 kW

SCOP

4.12

ηsh

161.80 %

Ph PL CondA

15.12 kW

COP PL CondA

1.95

Ph PL CondB

9.20 kW

COP PL CondB

4.24

Ph PL CondC

5.92 kW

COPC

6.09

Ph PL CondD

7.05 kW

COP PL CondD

8.05

TOL

-10.0000 °C

Ph PL CondE TOL

17.0900 kW

COP PL CondE TOL

1.6600

Tbiv

-10.00 °C

Ph PL CondF Tbiv

17.09 kW

COP PL CondF Tbiv

1.66

Psbc

69.00 W

Poffc

69.00 W

Ptoc

29.00 W

Pckc

0.00 W

Psbh

146.00 W

Poffh

69.00 W

Ptoh

129.00 W

Pckh

29.00 W

LwO env

80.00 dB(A)

LwO env in heating

84.00 dB(A)

CcpLRcontminh

1.5000

LRcontminh

0.1800

IU Names

PEFY-M50VMA-A1 / PEFY-M50VMA-A1 / PEFY-M50VMA-A1 / PEFY-M50VMA-A1 / PEFY-M50VMA-A1 / PEFY-M50VMA-A1

Mounting

Ducted

Refrigerant

R410A

Main Power Supply

400-3-50

Cd

0.2500