Air conditioners - Air to air, multi split, reversible (> 12 kW)

Model FDC125VNA-W/FDT60VH/FDT60VH

Range

VNA-W/VSA-W (AC2 multi)

Diploma nb.

17.02.280

Participant

2208

Brand

MHI Thermal Systems

Pc

12.50 kW

EER

3.30

Pec

3.79 kW

Ph

14.00 kW

Peh

3.31 kW

COP

4.23

Pdesignc

12.50 kW

SEER

7.96

ηsc

315.40 %

Pc PL CondB

9.20 kW

EER PL CondB

5.19

Pc PL CondC

5.90 kW

EER PL CondC

9.50

Pc PL CondD

3.60 kW

EER PL CondD

19.60

Pdesignh

9.80 kW

SCOP

5.20

ηsh

205.00 %

Ph PL CondA

8.70 kW

COP PL CondA

3.28

Ph PL CondB

5.30 kW

COP PL CondB

5.08

Ph PL CondC

3.40 kW

COP PL CondC

6.62

Ph PL CondD

3.00 kW

COP PL CondD

9.85

Tbiv

-10 °C

Ph PL CondF Tbiv

9.80 kW

COP PL CondF Tbiv

2.70

Psbc

8.00 W

Poffc

8.00 W

Ptoc

0.00 W

Pckc

5.00 W

Psbh

8.00 W

Poffh

8.00 W

Ptoh

20.00 W

Pckh

5.00 W

ηsh C

-3.0000 %

ηsh W

-3.0000 %

LwO env

71 dB(A)

LwI1 env

58 dB(A)

LwI2 env

58 dB(A)

LwO env in heating

71 dB(A)

LwI1 env in heating

58 dB(A)

LwI2 env in heating

58 dB(A)

IU Names

FDT60VH/FDT60VH

No. of IU

2

IU Range Names

FDT-VH

Mounting

Cassette

Refrigerant

R32

Factory Refrigerant Charge

3.3000 kg

Refr. Line

5 m

Corresponding Pipe Length

30.0000 m

Main Power Supply

230-1-50

Capacity Control

Variable