Variable refrigerant flow systems - Air cooled, reversible
Pc
45.00 kW
Pec
18.37 kW
EER
2.45
Ph
45.00 kW
Peh
12.47 kW
COP
3.61
SEER
6.33
ηsc
250.20 %
Pc PL CondB
30.65 kW
EER PL CondB
4.37
Pc PL CondC
19.54 kW
EER PL CondC
7.58
Pc PL CondD
9.76 kW
EER PL CondD
12.90
Pdesignh
30.83 kW
SCOP
3.58
ηsh
140.20 %
Ph PL CondA
27.27 kW
COP PL CondA
2.27
Ph PL CondB
16.80 kW
COP PL CondB
2.98
Ph PL CondC
10.09 kW
COPC
6.30
Ph PL CondD
8.13 kW
COP PL CondD
7.62
Tbiv
-7.00 °C
Ph PL CondF Tbiv
27.27 kW
COP PL CondF Tbiv
2.27
Psbc
40.00 W
Poffc
40.00 W
Ptoc
0.00 W
Pckc
0.00 W
Psbh
38.00 W
Poffh
36.00 W
Ptoh
46.00 W
Pckh
10.00 W
LwO env
87.00 dB(A)
LwO env in heating
87.00 dB(A)
IU Names
AVD-26UXCSCLXU
Mounting
ducted
Refrigerant
R410A
Main Power Supply
400-3-50
Cd
0.2500