Variable refrigerant flow systems - Air cooled, reversible
Pc
33.50 kW
Pec
8.98 kW
EER
3.73
Ph
37.50 kW
Peh
9.04 kW
COP
4.15
Pdesignc
33.5000 kW
SEER
7.40
ηsc
293.20 %
Pc PL CondB
24.60 kW
EER PL CondB
5.57
Pc PL CondC
15.80 kW
EER PL CondC
9.00
Pc PL CondD
10.70 kW
EER PL CondD
14.78
Pdesignh
22.20 kW
SCOP
4.68
ηsh
184.20 %
Ph PL CondA
19.00 kW
COP PL CondA
3.02
Ph PL CondB
12.00 kW
COP PL CondB
4.11
Ph PL CondC
7.70 kW
COPC
7.43
Ph PL CondD
6.50 kW
COP PL CondD
8.60
TOL
-10.0000 °C
Ph PL CondE TOL
18.3000 kW
COP PL CondE TOL
2.1700
Tbiv
-10.00 °C
Ph PL CondF Tbiv
22.20 kW
COP PL CondF Tbiv
2.76
Psbc
45.00 W
Poffc
45.00 W
Ptoc
50.00 W
Pckc
35.00 W
Psbh
45.00 W
Poffh
45.00 W
Ptoh
60.00 W
Pckh
35.00 W
LwO env
82.00 dB(A)
LwO env in heating
81.00 dB(A)
IU Names
FDT56KXZE1/FDT56KXZE1/FDT56KXZE1/FDT56KXZE1/FDT56KXZE1/FDT56KXZE1
Mounting
Cassette
Refrigerant
R410A
Main Power Supply
400-3-50
Cd
0.2500