Air conditioners - Air to air, split, reversible (≤ 12 kW)
Pc
3.00 kW
EER
4.35
Pec
0.69 kW
Ph
3.20 kW
Peh
0.72 kW
COP
4.45
Pdesignc
3.00 kW
SEER
7.50
SEER Class
A++
Qce
140.00 kWh/annum
Pc PL CondB
2.22 kW
EER PL CondB
6.17
Pc PL CondC
1.43 kW
EER PL CondC
9.46
Pc PL CondD
1.41 kW
EER PL CondD
10.21
Pdesignh
3.00 kW
SCOP
4.75
SCOP Class
A++
Qhe
884.00 kWh/annum
Ph PL CondA
2.66 kW
COP PL CondA
3.02
Ph PL CondB
1.62 kW
COP PL CondB
4.71
Ph PL CondC
1.09 kW
COP PL CondC
6.18
Ph PL CondD
1.07 kW
COP PL CondD
7.53
TOL
-30.0000 °C
Ph PL CondE TOL
3.00 kW
COP PL CondE TOL
2.50
Tbiv
-10 °C
Ph PL CondF Tbiv
3.00 kW
COP PL CondF Tbiv
2.50
Psbc
1.00 W
Poffc
1.00 W
Ptoc
9.00 W
Pckc
0.00 W
Psbh
1.00 W
Poffh
1.00 W
Ptoh
10.00 W
Pckh
0.00 W
SCOP Class C
G
SCOP Class W
G
LwO env
60 dB(A)
LwI1 env
53 dB(A)
LRcontminc
0.40
CcpLRcontminc
2.18
LRcontminh
0.35
CcpLRcontminh
1.39
IU Names
FVXTM30A
No. of IU
1
IU Range Names
FVXTM
Mounting
Wall mounted
Refrigerant
R32
Factory Refrigerant Charge
0.9700 kg
Refr. Line
5 m
Corresponding Pipe Length
10.0000 m
Main Power Supply
230-1-50
Capacity Control
variable
Eligible CEE
true