Heat pumps NF - Air to water, heating, cooling, and hot water

Model AWHP 6MR-FSCR 19P HYBRID V200

Gamma

OecOil-Hybrid Condens (Rotary)

Diploma

19.07.019

Participant

3162

Brand

OERTLI

LwO Env

65 dB(A)

LwI Env

49 dB(A)

Pdesignh (W55)

3.60 kW

SCOPnet (W55)

3.52

SCOP (W55)

3.49

ηs,h (W55)

138.00 %

Pdesignc

4.50 kW

SEER

3.95

Ph

3.96 kW

Pe

1.53 kW

COP

2.59

Ph

3.74 kW

Pe

1.11 kW

COP

3.37

Ph

5.82 kW

Pe

1.38 kW

COP

4.22

Ph

3.73 kW

Pe

1.81 kW

COP

2.06

Ph

3.67 kW

Pe

1.34 kW

COP

2.74

Ph

5.38 kW

Pe

1.66 kW

COP

3.24

Ph

3.45 kW

Pe

2.35 kW

COP

1.47

Ph

3.40 kW

Pe

1.55 kW

COP

2.19

Ph

5.53 kW

Pe

2.19 kW

COP

2.53

Pc

4.50 kW

Pe

1.66 kW

EER

2.71

Pc

7.41 kW

Pe

2.56 kW

EER

2.90

TOL (W55)

-10.00 °C

COP E (W55)

1.52

Tbiv (W55)

-10.00 °C

PhF (W55)

3.60 kW

COP F (W55)

1.52

Taux

1.09 %

Psbh

15.00 W

reference code

7642728

HP Detailed reference

AWHP 6 MR-2 & BALLON 200 PSL HYBRID 4-8 & FSC. 19

Tank Detailed reference

7623188-200 ESL HYBRID 4-8 EH500

LRcontmin

35.90 %

Ccp LRcontmin

1.02 %

Main Power Supply

230-1-50

Liquid Refrigerant

R410A

Type

Split

Location

Indoor

Tc

55 °C

Tapping Cycle NF (EN 16147)

L

Running Mode

Alternating

Nominal Stockage Volume

177 l

th

0h0min

Pes

35.00 W

0' (WH)

53.10 °C

V40

254 l

Qelec

4.29 kWh/day

AEC

899.00 kWh/annum

COP (DHW)

2.72

η WH

114.00 %

th

0h0min

Compressor system

Variable

Compressor Type

Rotary