Variable refrigerant flow systems - Air cooled, reversible

Model AW-YEVFD220-H16

Range

Flow Logic IV

Diploma nb.

18.06.004

Participant

AIRWELL RESIDENTIAL SAS

Brand

AIRWELL

Pc

22.60 kW

Pec

7.74 kW

EER

2.92

Ph

22.60 kW

Peh

6.44 kW

COP

3.51

Pdesignc

22.6000 kW

SEER

5.60

ηsc

221.00 %

Pc PL CondB

16.72 kW

EER PL CondB

4.50

Pc PL CondC

10.62 kW

EER PL CondC

6.40

Pc PL CondD

4.75 kW

EER PL CondD

7.90

Pdesignh

12.00 kW

SCOP

3.64

ηsh

142.60 %

Ph PL CondA

10.60 kW

COP PL CondA

2.60

Ph PL CondB

6.50 kW

COP PL CondB

3.38

Ph PL CondC

4.20 kW

COPC

4.82

Ph PL CondD

2.25 kW

COP PL CondD

5.58

TOL

-10.0000 °C

Ph PL CondE TOL

12.0000 kW

COP PL CondE TOL

2.4000

Tbiv

-7.00 °C

Ph PL CondF Tbiv

10.60 kW

COP PL CondF Tbiv

2.60

Psbc

20.00 W

Poffc

20.00 W

Ptoc

20.00 W

Pckc

0.00 W

Psbh

20.00 W

Poffh

20.00 W

Ptoh

20.00 W

Pckh

0.00 W

LwO env

81.00 dB(A)

LwO env in heating

83.00 dB(A)

IU Names

4xCVTA-050/045N-01M22

Mounting

Cassette

Refrigerant

R410A

Main Power Supply

400-3-50