Variable refrigerant flow systems - Air cooled, reversible

Model ARV-H140/NR1-E

Range

ARV-H-/NR1-E

Diploma nb.

19.11.005

Participant

1294

Brand

AUX

Pc

12.77 kW

Pec

3.74 kW

EER

3.41

Ph

16.00 kW

Peh

3.82 kW

COP

4.19

Pdesignc

12.7700 kW

SEER

6.65

ηsc

263.00 %

Pc PL CondB

10.20 kW

EER PL CondB

4.33

Pc PL CondC

6.74 kW

EER PL CondC

7.94

Pc PL CondD

3.04 kW

EER PL CondD

9.44

Pdesignh

10.00 kW

SCOP

4.84

ηsh

190.60 %

Ph PL CondA

10.56 kW

COP PL CondA

2.73

Ph PL CondB

5.60 kW

COP PL CondB

5.20

Ph PL CondC

3.50 kW

COPC

6.09

Ph PL CondD

1.48 kW

COP PL CondD

4.00

TOL

-10.0000 °C

Ph PL CondE TOL

10.0000 kW

COP PL CondE TOL

4.4800

Tbiv

-7.00 °C

Ph PL CondF Tbiv

10.56 kW

COP PL CondF Tbiv

2.73

Psbc

21.60 W

Poffc

21.60 W

Ptoc

21.60 W

Pckc

21.60 W

Psbh

21.60 W

Poffh

21.60 W

Ptoh

21.60 W

Pckh

21.60 W

LwO env

68.00 dB(A)

LwO env in heating

68.00 dB(A)

IU Names

ARVMD-H036/NR1DM-E*4

Mounting

Ducted

Refrigerant

R410A

Main Power Supply