Variable refrigerant flow systems - Air cooled, reversible

Model UEHM 054 PMB1

Gamma

GENESIS

Diploma

24.11.008

Participant

Atlantic Climatisation et Traitement d'Air Commerce

Brand

ATLANTIC

Pc

15.50 kW

Pec

4.80 kW

EER

3.23

Ph

15.50 kW

Peh

4.08 kW

COP

3.80

Pdesignc

15.5000 kW

SEER

7.62

ηsc

301.80 %

Pc PL CondB

11.47 kW

EER PL CondB

5.12

Pc PL CondC

7.29 kW

EER PL CondC

9.79

Pc PL CondD

3.26 kW

EER PL CondD

13.60

Pdesignh

10.20 kW

SCOP

4.71

ηsh

185.40 %

Ph PL CondA

9.01 kW

COP PL CondA

2.90

Ph PL CondB

5.50 kW

COP PL CondB

4.58

Ph PL CondC

3.57 kW

COPC

6.62

Ph PL CondD

2.51 kW

COP PL CondD

10.35

TOL

-10.0000 °C

Ph PL CondE TOL

10.2000 kW

COP PL CondE TOL

2.4000

Tbiv

-7.00 °C

Ph PL CondF Tbiv

9.01 kW

COP PL CondF Tbiv

2.90

Psbc

23.00 W

Poffc

23.00 W

Ptoc

23.00 W

Pckc

0.00 W

Psbh

25.00 W

Poffh

25.00 W

Ptoh

25.00 W

Pckh

0.00 W

LwO env

71.50 dB(A)

LwO env in heating

73.50 dB(A)

CcpLRcontminc

2.9300

LRcontminc

0.4000

CcpLRcontminh

1.7400

LRcontminh

0.1900

IU Names

3xUIC 12 HIB1+UIC 16 HIB1

Mounting

Cassette

Refrigerant

R32

Main Power Supply

230-1-50