Variable refrigerant flow systems - Air cooled, reversible

Model AM180AXVAGH

Gamma

DVM S2

Diploma

24.06.007

Participant

3640

Brand

SAMSUNG

Pc

50.40 kW

Pec

22.60 kW

EER

2.23

Ph

50.40 kW

Peh

15.09 kW

COP

3.34

SEER

6.38

ηsc

252.20 %

Pc PL CondB

37.30 kW

EER PL CondB

4.00

Pc PL CondC

23.70 kW

EER PL CondC

7.30

Pc PL CondD

10.60 kW

EER PL CondD

19.60

Pdesignh

26.50 kW

SCOP

4.16

ηsh

163.40 %

Ph PL CondA

23.30 kW

COP PL CondA

2.40

Ph PL CondB

14.30 kW

COP PL CondB

3.90

Ph PL CondC

9.30 kW

COPC

6.40

Ph PL CondD

4.00 kW

COP PL CondD

6.90

Tbiv

-10.00 °C

Ph PL CondF Tbiv

26.50 kW

COP PL CondF Tbiv

2.20

Psbc

30.00 W

Poffc

30.00 W

Ptoc

0.00 W

Pckc

0.00 W

Psbh

30.00 W

Poffh

30.00 W

Ptoh

30.00 W

Pckh

62.00 W

LwO env

83.00 dB(A)

LwO env in heating

86.00 dB(A)

IU Names

AM028AN4PKH + AM036AN4PKH + AM045AN4PKH + 2x AM056AN4PKH + 2x AM090AN4PKH + AM128AN4PKH

Mounting

Cassette

Refrigerant

R410A

Main Power Supply

400-3-50