Pompes à chaleur Air-Air - Air/air, split, réversible (≤ 12 kW)

Model PUZ-M100VKA2/PKA-M100KAL2

Gamme

P series

N° de diplôme

94.01.069

Participant

44

Brand

MITSUBISHI ELECTRIC

Pc

9.50 kW

EER

3.23

Pec

2.94 kW

Ph

11.20 kW

Peh

3.28 kW

COP

3.41

Pdesignc

9.50 kW

SEER

5.80

SEER Class

A+

Qce

573.00 kWh/annum

Pc PL CondB

7.00 kW

EER PL CondB

4.40

Pc PL CondC

4.50 kW

EER PL CondC

7.90

Pc PL CondD

4.00 kW

EER PL CondD

10.20

Pdesignh

8.00 kW

SCOP

4.00

SCOP Class

A+

Qhe

2780.00 kWh/annum

Ph PL CondA

7.00 kW

COP PL CondA

2.50

Ph PL CondB

4.30 kW

COP PL CondB

3.90

Ph PL CondC

2.80 kW

COP PL CondC

5.70

Ph PL CondD

3.20 kW

COP PL CondD

7.00

TOL

-15.0000 °C

Ph PL CondE TOL

4.50 kW

COP PL CondE TOL

1.80

Tbiv

-7 °C

Ph PL CondF Tbiv

7.00 kW

COP PL CondF Tbiv

2.50

Psbc

22.00 W

Poffc

22.00 W

Ptoc

7.00 W

Poffh

22.00 W

Ptoh

75.00 W

SCOP Class C

G

SCOP Class W

G

LwO env

70 dB(A)

LwI1 env

65 dB(A)

IU Names

PKA-M100KAL2

No. of IU

1

IU Range Names

PKA

Mounting

Wall mounted

Refrigerant

R32

Factory Refrigerant Charge

3.1000 kg

Refr. Line

5m m

Corresponding Pipe Length

30.0000 m

Main Power Supply

230-1-50

Capacity Control

Variable

Eligible CEE

true