Pompes à chaleur Air-Air - Air/air, multi split, réversible (> 12 kW)
Pc
19.00 kW
EER
3.37
Pec
5.64 kW
Ph
22.40 kW
Pdesignc
19.00 kW
SEER
7.39
ηsc
292.60 %
Pc PL CondB
14.00 kW
EER PL CondB
5.53
Pc PL CondC
9.00 kW
EER PL CondC
9.87
Pc PL CondD
4.88 kW
EER PL CondD
12.70
Pdesignh
11.20 kW
SCOP
4.15
ηsh
163.00 %
Ph PL CondA
9.91 kW
COP PL CondA
2.56
Ph PL CondB
6.03 kW
COP PL CondB
3.77
Ph PL CondC
3.88 kW
COP PL CondC
6.52
Ph PL CondD
3.82 kW
COP PL CondD
7.13
Tbiv
-10 °C
Ph PL CondF Tbiv
11.20 kW
COP PL CondF Tbiv
2.36
Psbc
24.00 W
Poffc
24.00 W
Ptoc
18.00 W
Pckc
24.00 W
Psbh
33.00 W
Poffh
33.00 W
Ptoh
45.00 W
Pckh
24.00 W
ηsh C
-3.0000 %
ηsh W
-3.0000 %
LwO env
73 dB(A)
LwI1 env
59 dB(A)
LwO env in heating
76 dB(A)
IU Names
FUA71A
No. of IU
3
IU Range Names
FUA
Mounting
Ceiling suspended
Refrigerant
R32
Factory Refrigerant Charge
5.0000 kg
Refr. Line
5 m m
Corresponding Pipe Length
30.0000 m
Main Power Supply
400-3-50
Capacity Control
variable