Variable refrigerant flow systems - Air cooled, reversible
Pc
12.50 kW
Pec
4.34 kW
EER
2.88
Ph
14.00 kW
Peh
3.49 kW
COP
4.01
Pdesignc
12.5000 kW
SEER
6.43
ηsc
254.20 %
Pc PL CondB
9.21 kW
EER PL CondB
5.36
Pc PL CondC
5.92 kW
EER PL CondC
8.59
Pc PL CondD
5.40 kW
EER PL CondD
12.43
Pdesignh
10.00 kW
SCOP
4.30
ηsh
169.00 %
Ph PL CondA
8.85 kW
COP PL CondA
2.86
Ph PL CondB
5.38 kW
COP PL CondB
4.16
Ph PL CondC
4.30 kW
COPC
6.14
Ph PL CondD
5.20 kW
COP PL CondD
6.43
TOL
-20.0000 °C
Ph PL CondE TOL
7.1000 kW
COP PL CondE TOL
1.8200
Tbiv
-10.00 °C
Ph PL CondF Tbiv
10.00 kW
COP PL CondF Tbiv
2.36
Psbc
27.00 W
Poffc
27.00 W
Ptoc
25.00 W
Pckc
0.00 W
Psbh
27.00 W
Poffh
27.00 W
Ptoh
34.00 W
Pckh
0.00 W
LwO env
69.00 dB(A)
LwO env in heating
71.00 dB(A)
CcpLRcontminh
1.5300
LRcontminh
0.3100
IU Names
PLFY-M50VEM6-E / PLFY-M63VEM6-E
Mounting
Cassette
Refrigerant
R410A
Main Power Supply
400-3-50
Cd
0.2500