Variable refrigerant flow systems - Air cooled, reversible
Pc
28.00 kW
Pec
10.53 kW
EER
2.66
Ph
28.00 kW
Peh
7.24 kW
COP
3.87
Pdesignc
28.0000 kW
SEER
6.66
ηsc
263.40 %
Pc PL CondB
20.63 kW
EER PL CondB
4.40
Pc PL CondC
13.26 kW
EER PL CondC
7.80
Pc PL CondD
5.89 kW
EER PL CondD
16.50
Pdesignh
16.20 kW
SCOP
4.80
ηsh
189.00 %
Ph PL CondA
14.33 kW
COP PL CondA
3.00
Ph PL CondB
8.72 kW
COP PL CondB
4.60
Ph PL CondC
5.60 kW
COPC
6.55
Ph PL CondD
4.00 kW
COP PL CondD
8.40
TOL
-10.0000 °C
Ph PL CondE TOL
16.2000 kW
COP PL CondE TOL
2.4200
Tbiv
-10.00 °C
Ph PL CondF Tbiv
16.20 kW
COP PL CondF Tbiv
2.42
Psbc
20.00 W
Poffc
20.00 W
Ptoc
30.00 W
Pckc
10.00 W
Psbh
25.00 W
Poffh
25.00 W
Ptoh
40.00 W
Pckh
40.00 W
LwO env
84.00 dB(A)
LwO env in heating
83.00 dB(A)
IU Names
4x GMV-ND71PHS/B-T
Mounting
ducted
Refrigerant
R410A
Main Power Supply
400-3-50
Cd
0.2500