Variable refrigerant flow systems - Air cooled, reversible
Pc
22.40 kW
Pec
8.72 kW
EER
2.57
Ph
22.40 kW
Peh
5.79 kW
COP
3.87
Pdesignc
22.4000 kW
SEER
6.85
ηsc
271.00 %
Pc PL CondB
16.00 kW
EER PL CondB
4.80
Pc PL CondC
10.10 kW
EER PL CondC
8.70
Pc PL CondD
5.61 kW
EER PL CondD
20.00
Pdesignh
16.00 kW
SCOP
4.27
ηsh
167.80 %
Ph PL CondA
14.15 kW
COP PL CondA
2.70
Ph PL CondB
8.50 kW
COP PL CondB
3.70
Ph PL CondC
5.54 kW
COPC
6.80
Ph PL CondD
3.50 kW
COP PL CondD
9.60
TOL
-7.0000 °C
Ph PL CondE TOL
14.1500 kW
COP PL CondE TOL
2.7000
Tbiv
-7.00 °C
Ph PL CondF Tbiv
14.15 kW
COP PL CondF Tbiv
2.70
Psbc
30.00 W
Poffc
30.00 W
Ptoc
57.00 W
Pckc
42.00 W
Psbh
30.00 W
Poffh
30.00 W
Ptoh
82.00 W
Pckh
42.00 W
LwO env
78.00 dB(A)
LwO env in heating
79.00 dB(A)
IU Names
4x GMV-ND56PHS/B-T
Mounting
ducted
Refrigerant
R410A
Main Power Supply
400-3-50
Cd
0.2500