Variable refrigerant flow systems - Air cooled, reversible

Model RXYSA10A

Gamma

RXYSA-A

Diploma

15.02.244

Participant

20

Brand

DAIKIN

Pc

28.00 kW

Pec

9.33 kW

EER

3.00

Ph

28.00 kW

Peh

7.31 kW

COP

3.83

Pdesignc

28.0000 kW

SEER

7.13

ηsc

282.20 %

Pc PL CondB

20.63 kW

EER PL CondB

4.99

Pc PL CondC

13.27 kW

EER PL CondC

7.73

Pc PL CondD

7.32 kW

EER PL CondD

18.82

Pdesignh

19.64 kW

SCOP

4.42

ηsh

173.80 %

Ph PL CondA

17.38 kW

COP PL CondA

2.70

Ph PL CondB

10.58 kW

COP PL CondB

4.45

Ph PL CondC

6.80 kW

COPC

6.05

Ph PL CondD

4.49 kW

COP PL CondD

5.52

TOL

-10.0000 °C

Ph PL CondE TOL

19.6400 kW

COP PL CondE TOL

2.3000

Tbiv

-10.00 °C

Ph PL CondF Tbiv

19.64 kW

COP PL CondF Tbiv

2.30

Psbc

46.00 W

Poffc

46.00 W

Ptoc

0.00 W

Pckc

0.00 W

Psbh

45.00 W

Poffh

45.00 W

Ptoh

51.00 W

Pckh

45.00 W

LwO env

74.00 dB(A)

LwO env in heating

74.00 dB(A)

CcpLRcontminc

2.5800

LRcontminc

0.4000

CcpLRcontminh

1.5800

LRcontminh

0.2400

IU Names

4x FXFA63A

Mounting

cassette

Refrigerant

R32

Main Power Supply

400-3-50

Cd

0.2500