Chillers & Heat pumps - Heat pump, air-to-water, packaged, reversible

Model i-290 0250-PS

Gamma

i-290 0240-0250

Diploma

15.02.241

Participant

1157

Brand

MAXA

Lw

83.0 dB(A)

Pc

34.10 kW

EER

3.10

Apc Indoor

128.00 kPa

SEER

4.81

ηsc

189.5 %

Water Regulation

FW/VO

Ph

50.10 kW

COP

4.21

Aph Indoor

81.10 kPa

Ph

47.90 kW

COP

2.90

Aph Indoor

139.70 kPa

Ph

45.90 kW

COP

2.43

Aph Indoor

153.00 kPa

Psbc

28.00 W

Pdesignh

43.00 kW

SCOP

4.20

ηsh

165.0 %

Water Regulation

FW/VO

Lw

75.0 dB(A)

Pdesignh

44.00 kW

SCOP

3.36

ηsh

131.0 %

Water Regulation

FW/VO

Lw

75.0 dB(A)

Pdesignh

42.00 kW

SCOP

2.88

ηsh

112.2 %

Water Regulation

FW/VO

Refrigerant

R290

Main Power Supply

400-3-50

Control of Pump Speed

Fixed

Outdoor Heat Exc. Type

Finned Tube

Outdoor Heat Exc. Type

Finned Tube

Indoor Heat Exc. Type

Plate

Indoor Heat Exc. Type

Plate

Expansion Valve Type

Electronic

Expansion Valve Type

Electronic

Unit Capacity Control

Variable

Unit Capacity Control

Variable

Type

Scroll

Type

Scroll

Inverter

true

Inverter

true

Number

2

Number

2