Variable refrigerant flow systems - Air cooled, reversible

Model 38VR0S7H112016(B)

Bereich

XPOWER SUPER XS(B) SERIES

Diplom-Nummer

17.09.016

Participant

1900

Brand

CARRIER

Pc

17.50 kW

Pec

7.14 kW

EER

2.45

Ph

19.00 kW

Peh

6.13 kW

COP

3.10

Pdesignc

17.5000 kW

SEER

6.50

ηsc

257.00 %

Qce

1640.93 kWh/annum

Pc PL CondB

12.86 kW

EER PL CondB

4.48

Pc PL CondC

8.29 kW

EER PL CondC

8.30

Pc PL CondD

5.83 kW

EER PL CondD

12.69

Pdesignh

10.20 kW

SCOP

4.25

ηsh

167.00 %

Ph PL CondA

9.38 kW

COP PL CondA

2.55

Ph PL CondB

5.71 kW

COP PL CondB

4.13

Ph PL CondC

3.80 kW

COPC

5.88

Ph PL CondD

4.29 kW

COP PL CondD

7.28

TOL

-10.0000 °C

Ph PL CondE TOL

10.6000 kW

COP PL CondE TOL

2.3000

Tbiv

-10.00 °C

Ph PL CondF Tbiv

10.60 kW

COP PL CondF Tbiv

2.30

Psbc

23.00 W

Poffc

23.00 W

Ptoc

2.00 W

Pckc

2.00 W

Psbh

23.00 W

Poffh

23.00 W

Ptoh

28.00 W

Pckh

2.00 W

LwO env

75.00 dB(A)

LwO env in heating

75.00 dB(A)

LwI1 duct in heating

64.0000 dB(A)

LwI2 duct in heating

64.0000 dB(A)

CcpLRcontminc

5.1800

LRcontminc

0.1000

CcpLRcontminh

2.3500

LRcontminh

0.1000

IU Names

4x 42VD016H115003016

Mounting

ducted

Refrigerant

R410A

Main Power Supply

230-1-50

Cd

0.2500