Variable refrigerant flow systems - Air cooled, reversible

Model MDV-V140WDN1

Bereich

MDV Series

Diplom-Nummer

16.05.007

Participant

GD MIDEA Heating & Ventilating Equipment Co. Ltd

Brand

MDV

Pc

14.00 kW

Pec

4.67 kW

EER

3.00

Ph

16.00 kW

Peh

5.18 kW

COP

3.09

Pdesignc

14.0000 kW

SEER

6.40

ηsc

253.00 %

Qce

1324.78 kWh/annum

Pc PL CondB

10.32 kW

EER PL CondB

5.26

Pc PL CondC

6.63 kW

EER PL CondC

7.27

Pc PL CondD

5.29 kW

EER PL CondD

11.31

Pdesignh

9.20 kW

SCOP

4.10

ηsh

161.00 %

Ph PL CondA

8.14 kW

COP PL CondA

2.41

Ph PL CondB

4.95 kW

COP PL CondB

3.92

Ph PL CondC

3.40 kW

COPC

6.00

Ph PL CondD

4.18 kW

COP PL CondD

7.42

TOL

-10.0000 °C

Ph PL CondE TOL

9.2000 kW

COP PL CondE TOL

2.0800

Tbiv

-10.00 °C

Ph PL CondF Tbiv

9.20 kW

COP PL CondF Tbiv

2.08

Psbc

23.00 W

Poffc

23.00 W

Ptoc

5.00 W

Pckc

5.00 W

Psbh

23.00 W

Poffh

23.00 W

Ptoh

28.00 W

Pckh

5.00 W

LwO env

76.00 dB(A)

LwO env in heating

76.00 dB(A)

LwI1 duct in heating

62.0000 dB(A)

LwI2 duct in heating

64.0000 dB(A)

CcpLRcontminc

3.7700

LRcontminc

0.1000

CcpLRcontminh

2.4000

LRcontminh

0.1000

IU Names

2x MDVI3A-28C4VR12E+2x MDVI3A-45C4VR12E(Q)

Mounting

ducted

Refrigerant

R410A

Main Power Supply

230-1-50

Cd

0.2500