Air conditioners - Air to air, split, reversible (≤ 12 kW)

Model RXM25R9 / FVXM25A

Bereich

RXM

Diplom-Nummer

94.01.087

Participant

20

Brand

DAIKIN

Pdesignc

2.40 kW

SEER

8.55

Qce

98.00 kWh/annum

SEER Class

A+++

Pdesignh

2.30 kW

SCOP

4.65

SCOP Class

A++

Qhe

693.00 kWh/annum

LwO env

59 dB(A)

LwI1 env

52 dB(A)

Pc

2.40 kW

Pec

0.54 kW

EER

4.47

Pc @ 30°C

1.77 kW

EER @ 30°C

6.50

Pc @ 25°C

1.23 kW

EER @ 25°C

10.51

Pc @ 20°C

1.18 kW

EER @ 20°C

14.90

Ph

3.40 kW

Peh

0.75 kW

COP

4.55

Ph @ -7°C

2.04 kW

COP @ -7°C

3.46

Ph @ +2°C

1.24 kW

COP @ 2°C

4.67

Ph @ +7°C

1.02 kW

COP @ +7°C

5.67

Ph @ +12°C

1.06 kW

COP @ +12°C

7.16

Tbiv

-7 °C

Ph TBiv

2.04 kW

COP @ Tbiv

3.46

TOL

-15.00 °C

Ph E

2.01 kW

COP E

2.24

Poff

1.00 W

Psb

1.00 W

Pto

6.00 W

Pck

0.00 W

Poffh

1.00 W

Psbh

1.00 W

Ptoh

8.00 W

Pckh

0.00 W

Refrigerant

R32

Refr. Line

5 m m

Main Power Supply

230-1-50

Mounting

Floor standing

Capacity Control

variable

Corresponding Pipe Length

10.0000 m

Factory Refrigerant Charge

0.7600 kg

Inverter

true

Eligible CEE

true