Variable refrigerant flow systems - Air cooled, reversible
Pc
33.50 kW
Pec
13.96 kW
EER
2.40
Ph
33.50 kW
Peh
9.41 kW
COP
3.56
Pdesignc
33.5000 kW
SEER
6.31
ηsc
249.40 %
Pc PL CondB
24.68 kW
EER PL CondB
4.05
Pc PL CondC
15.86 kW
EER PL CondC
7.28
Pc PL CondD
7.05 kW
EER PL CondD
17.50
Pdesignh
18.50 kW
SCOP
4.40
ηsh
173.00 %
Ph PL CondA
16.36 kW
COP PL CondA
2.50
Ph PL CondB
9.96 kW
COP PL CondB
4.20
Ph PL CondC
6.40 kW
COPC
6.30
Ph PL CondD
3.68 kW
COP PL CondD
8.00
TOL
-10.0000 °C
Ph PL CondE TOL
18.5000 kW
COP PL CondE TOL
2.5000
Tbiv
-10.00 °C
Ph PL CondF Tbiv
18.50 kW
COP PL CondF Tbiv
2.50
Psbc
20.00 W
Poffc
20.00 W
Ptoc
30.00 W
Pckc
10.00 W
Psbh
25.00 W
Poffh
25.00 W
Ptoh
40.00 W
Pckh
40.00 W
LwO env
86.00 dB(A)
LwO env in heating
80.00 dB(A)
IU Names
6x GMV-ND56PHS/B-T
Mounting
ducted
Refrigerant
R410A
Main Power Supply
400-3-50
Cd
0.2500