Air conditioners - Air to air, split, reversible (≤ 12 kW)
Pc
5.00 kW
EER
3.68
Pec
1.36 kW
Ph
5.80 kW
Peh
1.45 kW
COP
4.00
Pdesignc
5.00 kW
SEER
7.33
SEER Class
A++
Qce
239.00 kWh/annum
Pc PL CondB
3.68 kW
EER PL CondB
5.29
Pc PL CondC
2.37 kW
EER PL CondC
9.24
Pc PL CondD
1.87 kW
EER PL CondD
12.03
Pdesignh
4.00 kW
SCOP
4.60
SCOP Class
A++
Qhe
1217.00 kWh/annum
Ph PL CondA
3.54 kW
COP PL CondA
3.16
Ph PL CondB
2.15 kW
COP PL CondB
4.43
Ph PL CondC
1.71 kW
COP PL CondC
6.32
Ph PL CondD
1.52 kW
COP PL CondD
7.25
TOL
-15.0000 °C
Ph PL CondE TOL
4.12 kW
COP PL CondE TOL
2.16
Tbiv
-7 °C
Ph PL CondF Tbiv
3.54 kW
COP PL CondF Tbiv
3.16
Psbc
1.00 W
Poffc
1.00 W
Ptoc
12.00 W
Pckc
0.00 W
Psbh
1.00 W
Poffh
1.00 W
Ptoh
13.00 W
Pckh
0.00 W
SCOP Class C
G
SCOP Class W
G
LwO env
62 dB(A)
LwI1 env
60 dB(A)
IU Names
FTXA50BS
No. of IU
1
IU Range Names
FTXA
Mounting
Wall mounted
Refrigerant
R32
Factory Refrigerant Charge
1.1000 kg
Refr. Line
5 m
Corresponding Pipe Length
10.0000 m
Main Power Supply
230-1-50
Capacity Control
variable
Eligible CEE
true