Chillers & Heat pumps - Heat pump, air-to-water, packaged, reversible
Software name
CH Design
Software version
Version 2.13
Factory city
Cantarana di Cona (VE)
Factory country
Italy
Lw
98.0 dB(A)
Pc
224.87 kW
EER
2.54
Dpc Indoor
30.80 kPa
SEER
4.10
ηsc
161.0 %
Water Regulation
FW/VO
Ph
236.58 kW
COP
2.97
Dph Indoor
36.13 kPa
Refrigerant
R410A
Main Power Supply
400-3-50
Control of Pump Speed
No Pump
Unit Capacity Control
Staged
Type
Scroll
Number
4