Air handling units - Model box

Model Premium Line RW TB 50mm

نطاق

ATC

رقم الدبلوم

16.09.001

Participant

1718

Brand

ATC

Software name

ATC HVAC Calculator

Software version

2.2.3.100

Factory city

İzmir

Factory country

Turkey

Sub Range

ATC Premium Line

Panel thickness

50.00 mm

Insulation material [RW, PU, ...]

RW

Insulation material conductivity

0.0370 W/(m.K)

CS class

D1(M)

CAL class @ -400 Pa

L1(M)

CAL Class @ +700 Pa

L1(M)

FBL class

F9(M)

TT class

T2

TBF class

TB2

Casing accoustical insulation at 125 Hz

23 dB

Casing accoustical insulation at 250 Hz

21 dB

Casing accoustical insulation at 500 Hz

24 dB

Casing accoustical insulation at 1000 Hz

28 dB

Casing accoustical insulation at 2000 Hz

30 dB

Casing accoustical insulation at 4000 Hz

35 dB

Casing accoustical insulation at 8000 Hz

42 dB