Variable refrigerant flow systems - Air cooled, reversible
Pc
25.20 kW
Pec
7.80 kW
EER
3.23
Ph
25.20 kW
Peh
6.25 kW
COP
4.03
Pdesignc
25.2000 kW
SEER
7.41
ηsc
293.40 %
Qce
2041.14 kWh/annum
Pc PL CondB
18.57 kW
EER PL CondB
4.81
Pc PL CondC
11.94 kW
EER PL CondC
8.56
Pc PL CondD
7.35 kW
EER PL CondD
17.45
Pdesignh
13.70 kW
SCOP
4.45
ηsh
175.00 %
Ph PL CondA
12.12 kW
COP PL CondA
2.63
Ph PL CondB
7.38 kW
COP PL CondB
4.24
Ph PL CondC
5.30 kW
COPC
6.56
Ph PL CondD
6.26 kW
COP PL CondD
8.37
TOL
-10.0000 °C
Ph PL CondE TOL
13.7000 kW
COP PL CondE TOL
2.1600
Tbiv
-10.00 °C
Ph PL CondF Tbiv
13.70 kW
COP PL CondF Tbiv
2.16
Psbc
5.00 W
Poffc
5.00 W
Ptoc
5.00 W
Pckc
5.00 W
Psbh
5.00 W
Poffh
5.00 W
Ptoh
5.00 W
Pckh
5.00 W
LwO env
78.00 dB(A)
LwO env in heating
78.00 dB(A)
CcpLRcontminc
5.4000
LRcontminc
0.1000
CcpLRcontminh
2.0800
LRcontminh
0.1000
IU Names
1x CNT2-3Q-XY D45+3x CNT2-3Q-XY D71
Mounting
ducted
Refrigerant
R410A
Main Power Supply
400-3-50
Cd
0.2500