Variable refrigerant flow systems - Air cooled, reversible
Pc
22.40 kW
Pec
7.97 kW
EER
2.81
Ph
22.40 kW
Peh
7.23 kW
COP
3.10
Pdesignc
22.4000 kW
SEER
6.82
ηsc
269.80 %
Pc PL CondB
15.80 kW
EER PL CondB
4.91
Pc PL CondC
10.48 kW
EER PL CondC
8.97
Pc PL CondD
5.03 kW
EER PL CondD
15.72
Pdesignh
16.50 kW
SCOP
4.31
ηsh
169.40 %
Ph PL CondA
13.75 kW
COP PL CondA
2.33
Ph PL CondB
8.94 kW
COP PL CondB
3.85
Ph PL CondC
5.70 kW
COPC
7.41
Ph PL CondD
3.74 kW
COP PL CondD
9.52
TOL
-7.0000 °C
Ph PL CondE TOL
13.7500 kW
COP PL CondE TOL
2.3300
Tbiv
-7.00 °C
Ph PL CondF Tbiv
13.75 kW
COP PL CondF Tbiv
2.33
Psbc
30.00 W
Poffc
30.00 W
Ptoc
57.00 W
Pckc
42.00 W
Psbh
30.00 W
Poffh
30.00 W
Ptoh
82.00 W
Pckh
42.00 W
LwO env
78.00 dB(A)
LwO env in heating
79.00 dB(A)
IU Names
4x ACMI-56VRDC1D
Mounting
cassette
Refrigerant
R410A
Main Power Supply
400-3-50
Cd
0.2500