Variable refrigerant flow systems - Air cooled, reversible

Model AER-CS500CROU

Rango

CRF Series

Número de diploma

18.02.005

Participant

Qingdao Hisense Hitachi Air-Conditioning Systems Co. Ltd.

Brand

AEROSTAR

Pc

50.00 kW

Pec

21.46 kW

EER

2.33

Ph

50.00 kW

Peh

15.48 kW

COP

3.23

Pdesignc

50.0000 kW

SEER

6.14

ηsc

242.50 %

Qce

0.00 kWh/annum

Pc PL CondB

37.00 kW

EER PL CondB

4.51

Pc PL CondC

23.50 kW

EER PL CondC

7.76

Pc PL CondD

10.50 kW

EER PL CondD

10.40

Pdesignh

31.09 kW

SCOP

4.00

Qhe

0.00 kWh/annum

ηsh

156.90 %

Ph PL CondA

27.50 kW

COP PL CondA

2.09

Ph PL CondB

16.72 kW

COP PL CondB

3.74

Ph PL CondC

10.75 kW

COPC

6.30

Ph PL CondD

6.84 kW

COP PL CondD

8.19

TOL

-10.0000 °C

Ph PL CondE TOL

31.0700 kW

COP PL CondE TOL

2.0700

Tbiv

-7.00 °C

Ph PL CondF Tbiv

27.50 kW

COP PL CondF Tbiv

2.09

Psbc

38.00 W

Poffc

38.00 W

Ptoc

10.00 W

Pckc

10.00 W

Psbh

46.00 W

Poffh

46.00 W

Ptoh

46.00 W

Pckh

10.00 W

LwO env

87.00 dB(A)

LwO duct

0.00 dB(A)

LwI1 duct

58 dB(A)

LwI2 duct

58 dB(A)

LwO env in heating

87.00 dB(A)

LwO duct in heating

0.00 dB(A)

LwI2 env in heating

0.0000 dB(A)

LwI1 duct in heating

58.0000 dB(A)

LwI2 duct in heating

58.0000 dB(A)

LwI1 env in heating

0.0000 dB(A)

IU Names

AVD-19HJFH(R) ,  AVD-24HJFH(Q)

Mounting

ducted

Refrigerant

R410A

Main Power Supply

400-3-50

Cd

0.2500