Variable refrigerant flow systems - Air cooled, reversible
Rango
DVM S2
Número de diploma
Participant
Samsung Electronics Air Conditioner Europe B.V
Brand
SAMSUNG
Pc
33.60 kW
Pec
11.79 kW
EER
2.85
Ph
33.60 kW
Peh
9.46 kW
COP
3.55
SEER
7.00
ηsc
277.00 %
Pc PL CondB
24.90 kW
EER PL CondB
4.40
Pc PL CondC
15.80 kW
EER PL CondC
8.00
Pc PL CondD
7.10 kW
EER PL CondD
18.20
Pdesignh
18.80 kW
SCOP
4.28
ηsh
168.20 %
Ph PL CondA
16.50 kW
COP PL CondA
2.50
Ph PL CondB
10.20 kW
COP PL CondB
4.10
Ph PL CondC
6.60 kW
COPC
6.30
Ph PL CondD
2.80 kW
COP PL CondD
7.50
Tbiv
-10.00 °C
Ph PL CondF Tbiv
18.80 kW
COP PL CondF Tbiv
2.10
Psbc
30.00 W
Poffc
30.00 W
Ptoc
0.00 W
Pckc
0.00 W
Psbh
30.00 W
Poffh
30.00 W
Ptoh
30.00 W
Pckh
62.00 W
LwO env
81.00 dB(A)
LwO env in heating
84.00 dB(A)
IU Names
2x AM028AN4PKH + 2x AM056AN4PKH + 2x AM090AN4PKH
Mounting
Cassette
Refrigerant
R410A
Main Power Supply
400-3-50