Chillers & Heat pumps - Heat pump, air-to-water, packaged, reversible

Model KEM-12 DVR

Rango

NEXUS

Número de diploma

16.12.021

Participant

2001

Brand

KAYSUN

Software name

Heat Pump Solution

Software version

4.1

Lw

70.0 dB(A)

Pc

11.60 kW

EER

3.10

Apc Indoor

19.90 kPa

SEER

5.00

ηsc

199.9 %

Water Regulation

VW/VO

Ph

12.50 kW

COP

3.70

Aph Indoor

22.63 kPa

Pc

12.20 kW

EER

4.60

Apc Indoor

21.74 kPa

SEER

7.73

ηsc

308.5 %

Water Regulation

VW/VO

Ph

12.20 kW

COP

4.90

Aph Indoor

21.74 kPa

Ph

12.00 kW

COP

3.00

Aph Indoor

7.71 kPa

Psbc

13.00 W

Psbh

13.00 W

Pdesignh

12.30 kW

SCOP

5.00

ηsh

200.1 %

Water Regulation

VW/VO

Lw

70.0 dB(A)

Pdesignh

12.50 kW

SCOP

3.55

ηsh

141.6 %

Water Regulation

VW/VO

Lw

70.0 dB(A)

Refrigerant

R32

Main Power Supply

230-1-50

Control of Pump Speed

Variable

Indoor Heat Exc. Type

Plate

Unit Capacity Control

Variable

Type

Twin Rotary

Inverter

true

Number

1