Chillers & Heat pumps - Polyvalent unit, air-cooled, 4-pipes

Model ERACS2-Q-G05/XL-CA/2022

Rango

ERACS2-Q

Número de diploma

17.04.017

Participant

2384

Brand

Climaveneta

Software name

ApplyMe

Software version

2.41.0 - 5.0.9.0 - 1.9.10.0

Lw

85.0 dB(A)

Pc

454.00 kW

EER

2.59

Dpc Indoor

23.60 kPa

Ph

492.00 kW

COP

3.28

Pc

482.00 kW

Ph

616.00 kW

TER W45

7.76

Refrigerant

R513A

Main Power Supply

400-3-50

Control of Pump Speed

No Pump

Unit Capacity Control

Variable

Type

Screw

Number

2