Air conditioners - Air to air, split, reversible (≤ 12 kW)

Model RXTP25R / FVXM25A

Bereich

RXTP

Diplom-Nummer

94.01.087

Participant

20

Brand

DAIKIN

Pdesignc

2.50 kW

SEER

6.50

Qce

135.00 kWh/annum

SEER Class

A++

Pdesignh

2.50 kW

SCOP

4.70

SCOP Class

A++

Qhe

744.00 kWh/annum

LwO env

61 dB(A)

LwI1 env

52 dB(A)

Pc

2.50 kW

Pec

0.66 kW

EER

3.81

Pc @ 30°C

1.85 kW

EER @ 30°C

5.42

Pc @ 25°C

1.56 kW

EER @ 25°C

8.74

Pc @ 20°C

1.49 kW

EER @ 20°C

9.54

Ph

3.20 kW

Peh

0.83 kW

COP

3.86

Ph @ -7°C

2.22 kW

COP @ -7°C

3.46

Ph @ +2°C

1.35 kW

COP @ 2°C

4.75

Ph @ +7°C

1.16 kW

COP @ +7°C

5.79

Ph @ +12°C

1.38 kW

COP @ +12°C

7.05

Tbiv

-10 °C

Ph TBiv

2.50 kW

COP @ Tbiv

2.87

TOL

-25.00 °C

Ph E

2.91 kW

COP E

1.42

Poff

2.00 W

Psb

2.00 W

Pto

8.00 W

Pck

0.00 W

Poffh

2.00 W

Psbh

2.00 W

Ptoh

10.00 W

Pckh

0.00 W

Refrigerant

R32

Refr. Line

5 m m

Main Power Supply

230-1-50

Mounting

Floor standing

Capacity Control

variable

Factory Refrigerant Charge

1.1000 kg

Inverter

true

Eligible CEE

true