Air conditioners - Air to air, multi split, reversible (≤ 12 kW)

Model FDC71VNX-W/FDT40VH/FDT40VH

Bereich

VNX-W/VSX-W (AC1 multi)

Diplom-Nummer

17.02.279

Participant

2208

Brand

MHI Thermal Systems

Pc

7.10 kW

EER

4.40

Pec

1.61 kW

Ph

8.00 kW

Peh

1.83 kW

COP

4.38

Pdesignc

7.10 kW

SEER

7.60

SEER Class

A++

Qce

509.51 kWh/annum

Pc PL CondB

5.05 kW

EER PL CondB

5.76

Pc PL CondC

3.30 kW

EER PL CondC

11.26

Pc PL CondD

2.05 kW

EER PL CondD

19.80

Pdesignh

5.80 kW

SCOP

4.66

SCOP Class

A++

Qhe

1742.00 kWh/annum

Ph PL CondA

5.13 kW

COP PL CondA

3.44

Ph PL CondB

3.00 kW

COP PL CondB

4.27

Ph PL CondC

2.00 kW

COP PL CondC

6.06

Ph PL CondD

1.58 kW

COP PL CondD

8.32

TOL

-20.0000 °C

Ph PL CondE TOL

5.00 kW

COP PL CondE TOL

2.50

Tbiv

-10 °C

Ph PL CondF Tbiv

5.80 kW

COP PL CondF Tbiv

3.10

Psbc

18.00 W

Poffc

18.00 W

Ptoc

20.00 W

Pckc

7.00 W

Psbh

26.00 W

Poffh

18.00 W

Ptoh

35.00 W

Pckh

7.00 W

SCOP Class C

G

SCOP Class W

G

LwO env

66 dB(A)

LwI1 env

59 dB(A)

LwI2 env

59 dB(A)

LRcontminh

0.25

CcpLRcontminh

1.38

IU Names

FDT40VH

No. of IU

2

IU Range Names

FDT-VH

Mounting

Cassette

Refrigerant

R32

Factory Refrigerant Charge

2.7500 kg

Refr. Line

5 m

Corresponding Pipe Length

30.0000 m

Main Power Supply

230-1-50

Capacity Control

Variable

Cd

0.25

Eligible CEE

true