Air conditioners - Air to air, split, reversible (≤ 12 kW)

Model AOHG14LUC/ASHG14LUCA

Bereich

ASH**L

Diplom-Nummer

94.01.198

Participant

30

Brand

GENERAL

Pc

4.20 kW

EER

3.40

Pec

1.24 kW

Ph

5.40 kW

Peh

1.38 kW

COP

3.91

Pdesignc

4.20 kW

SEER

6.78

SEER Class

A++

Qce

217.00 kWh/annum

Pc PL CondB

3.09 kW

EER PL CondB

5.27

Pc PL CondC

1.99 kW

EER PL CondC

8.91

Pc PL CondD

1.80 kW

EER PL CondD

13.44

Pdesignh

4.80 kW

SCOP

4.00

SCOP Class

A+

Qhe

1677.00 kWh/annum

Ph PL CondA

3.54 kW

COP PL CondA

2.81

Ph PL CondB

2.58 kW

COP PL CondB

3.83

Ph PL CondC

1.66 kW

COP PL CondC

6.02

Ph PL CondD

1.88 kW

COP PL CondD

6.99

TOL

-15.0000 °C

Ph PL CondE TOL

3.13 kW

COP PL CondE TOL

2.56

Tbiv

-4 °C

Ph PL CondF Tbiv

3.69 kW

COP PL CondF Tbiv

2.91

Psbc

5.00 W

Poffc

5.00 W

Ptoc

36.00 W

Pckc

0.00 W

Psbh

5.00 W

Poffh

5.00 W

Ptoh

12.00 W

Pckh

0.00 W

SCOP Class C

G

SCOP Class W

G

LwO env

65 dB(A)

LwI1 env

60 dB(A)

IU Names

ASYG14LUCA

No. of IU

1

IU Range Names

ASY**L

Mounting

Wall mounted

Refrigerant

R410A

Factory Refrigerant Charge

1.0500 kg

Refr. Line

5,0 m m

Corresponding Pipe Length

15.0000 m

Main Power Supply

230-1-50

Capacity Control

Valiable

Eligible CEE

true