Variable refrigerant flow systems - Air cooled, reversible

Model AJY090LELDH

Rango

J-IVL

Número de diploma

15.06.012

Participant

GENERAL HVAC Solutions Euro GmbH

Brand

FUJITSU

Pc

28.00 kW

Pec

8.31 kW

EER

3.37

Ph

28.00 kW

Peh

6.42 kW

COP

4.36

Pdesignc

28.0000 kW

SEER

7.36

ηsc

291.40 %

Pc PL CondB

20.63 kW

EER PL CondB

5.74

Pc PL CondC

13.26 kW

EER PL CondC

9.93

Pc PL CondD

7.64 kW

EER PL CondD

11.48

Pdesignh

23.10 kW

SCOP

4.80

ηsh

189.00 %

Ph PL CondA

20.43 kW

COP PL CondA

2.42

Ph PL CondB

12.44 kW

COP PL CondB

4.84

Ph PL CondC

8.00 kW

COPC

7.05

Ph PL CondD

6.75 kW

COP PL CondD

9.04

TOL

-20.0000 °C

Ph PL CondE TOL

16.8200 kW

COP PL CondE TOL

1.9300

Tbiv

-7.00 °C

Ph PL CondF Tbiv

20.43 kW

COP PL CondF Tbiv

2.42

Psbc

19.00 W

Poffc

19.00 W

Ptoc

38.00 W

Pckc

38.00 W

Psbh

26.00 W

Poffh

26.00 W

Ptoh

64.00 W

Pckh

38.00 W

LwO env

69.00 dB(A)

LwO env in heating

70.00 dB(A)

IU Names

ARXP018GLFH x2 + ARXP030GLFH x2

Mounting

Ducted

Refrigerant

R410A

Main Power Supply

400-3-50

Capacity Control

Variable

Cd

0.2500