You can select a Certification Programme from the list below to retrieve its description (scope of the programme, definitions...)

  Постмотреть сертифицированные продукты


 
Scope of the programme

Are included in the scope:
- Outdoor units used in Variable Refrigerant Flow systems with the following characteristics:
   o Air or water source,
   o Reversible, heating-only and cooling-only.

Are excluded from the scope:
- VRF systems with data declared and published as combinations.
- Multiple module outdoor units.
- Units not fulfilling the requirements of Regulation 2016/2281.

Heat recovery units are included in the scope but the heat recovery function is not certified.
High ambient systems are included in the scope but tested under standard conditions as specified in RS 6/C/008.

Certify-all: The programme covers all VRF systems with the limitation of cooling capacities of approved independent laboratories. The company participating to this certification programme shall certify all standard production models below the following cooling capacity at standard conditions:

 Capacity

 Max No. of connected indoors

 

 Ducted horizontal

 Cassette

P ≤ 12 kW

 4

2

12 ≤ P < 30 kW (in both modes)

4

4

30 (in one mode) ≤ P < 50 kW (in both modes)

6

6

 50 (in one mode) ≤ P ≤ 100 kW
(in both modes)

 8

8

Definitions

Definitions given in EN 14511-3:2013 and EN 14511-3:2013 Annex I apply.
Definitions given in EN 14825:2016 apply.

In addition, the following definitions apply:

System capacity ratio:
Ratio of the total stated cooling (heating) capacity of all operating indoor units to the stated cooling (heating) capacity of the outdoor unit at the rating conditions.
Outdoor cooling capacity (Pc, outdoor)
Total cooling capacity of the outdoor unit measured as the total indoor cooling capacity unit
Outdoor heating capacity (Ph, outdoor)
Heating capacity of the outdoor unit measured as the total indoor heating capacity unit
Outdoor power input (Pe, outdoor)
Effective power input measured on the outdoor unit
Outdoor energy efficiency ratio (EERoutdoor)
Ratio of the outdoor cooling capacity to the outdoor power input
Outdoor energy efficiency ratio (COPoutdoor )
Ratio of the outdoor heating capacity to the outdoor power input

Testing requirements

Reference standard regarding thermal performances

Performance testing using the calorimeter room method:
EN 14511-3:2013 : “Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling”.

Performance testing using the air enthalpy method:
EN 14511-3:2013 :  “Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling”

Reference standard regarding seasonal thermal performances

EN 14825:2016 “Air conditioners, liquid chilling packages and heat pumps, with electrically driven compressors, for space heating and cooling. Testing and rating at part load conditions and calculation of seasonal performance”.

Reference standard regarding acoustical testing

EN 12102 “Air conditioners, liquid chilling packages, heat pumps and dehumidifiers with electrically driven compressors for space heating and cooling - Measurement of airborne noise - Determination of the sound power level” with exception of the duct end correction method described in section 6.2.2 of this standard.

Rating requirements

Rating requirements are in accordance with EN 14511.

The corrections of the total cooling capacity or heating capacity due to the power input of fans for indoor units with duct connection described in EN 14511-3 clause 4.1 shall not be carried out.

Performance are defined for a system capacity ratio equals to 100%.

Certified performance items

Nominal Efficiencies:
- Outdoor cooling capacity at standard rating condition
- Outdoor heating capacity at standard rating condition
- Effective power input (cooling and heating) at standard rating condition
- Outdoor EER at standard rating condition
- Outdoor COP at standard rating condition

Seasonal Efficiencies for Cooling
- Pdesignc
- SEER & ηsc

Seasonal Efficiencies for Heating
- Pdesignh
- SCOP & ηsh

Acoustics
- Sound power level in cooling
- Sound power level in heating (only for reversible units)

  • A-weighted outdoor side sound power
  • A-weighted sound power radiated from the duct (ducted units)
Reference documents


Certification Manual 13th (Novembre 2016)


OM-15-2018


RS-6c008-2018