You can select a Certification Programme from the list below to retrieve its description (scope of the programme, definitions...)

  Постмотреть сертифицированные продукты


 
Scope of the programme

           The present certification programme covers IT Cooling Units specifically designed and used to regulate air temperature and optionally air humidity of an enclosed space containing critical equipment such as IT equipment or telecommunication equipment.

The IT Cooling technologies considered in the scheme are Computer Room Air Conditioners Direct Expansion (CRAC) and Computer Room Air Conditioner Chilled Water (CRAH). HYBRID technologies pairing these technologies are also covered by the scope as an option.

Are excluded from the scope:

  • Packaged CRAC air cooled units
  • Multi-Split units
  • Partial IT Cooling units without any fan

The IT cooling units must be factory made units designed as a single packaged unit or a single split unit. Units must be 50 Hz frequency units, optionally 60 Hz units can be declared in addition to the 50 Hz. The units can be ducted or non-ducted units, as well on the air return or on the air supply. Floating floors air return or supply are considered as a duct.

Three air flow configurations of cooling are covered:

  • ROOM Based Cooling unit
  • ROW Based Cooling Unit
  • RACK Based Cooling Unit

The air flow direction can be:

  • Down-flow
  • Up-flow
  • Horizontal-flow
Programme features

The IT Cooling Unit certification that includes:

  •  Annual random selection of units and tests in an independent and   accredited laboratory
  • Annual production site audit
  • Software certification extending the certification from standard functioning conditions to non-standard conditions
Definitions

Computer Room Air Conditioner Direct Expansion (CRAC)

IT Cooling unit using dedicated electrically driven compressors and refrigerant cooling coils.

Computer Room Air Conditioner Chilled Water (CRAH)

IT Cooling Unit using water coils for cooling without any dedicated compressors and refrigerant cooling coils.

Down-flow

Air passes vertically downward through cooling coil. Return air enters the top of the unit and supply air leaves at the bottom or the front of the unit.

Horizontal-flow

Air passes horizontally through cooling coil. Return air enters the rear of the unit and supply air leaves at the front or the lateral side of the unit

Up-flow

Air passes vertically upward through cooling coil. Return air enters from the bottom or front of the unit and supply air leaves at the top of the unit

Single Packaged Unit

Factory assembly of components of a refrigeration system designed to be installed together and suitably fixed on a common mounting to form a single unit.

Single split unit

Factory assembly of components of refrigeration system fixed on two mountings to form a discrete matched functional unit

Codification

The present codification is used in the scheme:

Airflow configuration

Code

Computer Room Air Conditioner

CRAC

Computer Room Air Handler

CRAH

Heat rejection

Code

Air Cooled

A

Water Cooled

W

Mounting

Code

Single packaged unit

P

Single Split unit

S

Air flow direction

Code

Down-flow

D

Up-flow

U

Horizontal-flow

H

Air flow configuration

Code

Room based cooling

RM

Rack based cooling

RK

Row based cooling

RW

Testing requierements

The laboratory tests are performed according to the following standards:

For CRAC technologies
:

  • prEN 14511:2018 - 4 parts Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling
  • EN 12102:2013 Air conditioners, liquid chilling packages, heat pumps and dehumidifiers with electrically driven compressors for space heating and cooling. Measurement of airborne noise. Determination of the sound power level

For CRAH technologies:

  • EN 1397:2015 Heat exchangers. Hydronic room fan coil units. Test procedures for establishing the performance
  • EN 16583:2015 Heat exchangers. Hydronic room fan coils units. Determination of the sound power level

In complement to the EN standards the following ASHRAE standards are applied:

  • ANSI/ASHRAE Standard 127-2012 Method of Testing for Rating Computer and Data Processing Room Unitary Air Conditioners
  • ASHRAE Standard 37 Methods of Testing for Rating Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment
Certified performances

The performances certified are the following:

Certified performance

Unit

Symbol

1

Net Total Cooling Capacity

kW

 Pc

2

Net Sensible Cooling Capacity

kW

 Ps

3

Power input

kW

 Pe

4

A-weighted sound power indoor side

dB(A)

 Lw-in

5

A-weighted sound power radiated by duct

dB(A)

 Lw-du

6

A-weighted sound power outdoor side

dB(A)

 Lw-out

7

Water pressure drop

Pa

 Dpc

8

Supply Air Flow

m3/h

 Qv

9

Net EER

Energy Efficiency Ratio

 

W/W

EER

10

Net SHR

Sensible Heat Ratio

W/W

nSHR

Test conditions

Units are rated under standard and non-standard conditions.

The Standard conditions are the following

4 standard application classes of temperature are considered:

Class

Indoor Air Entering Dry Bulb Temperature

Indoor Air Entering Relative Humidity*

Class 1

24 °C

50%

Class 2

30 °C

35%

Class 3

35 °C

27%

Class 4

40 °C

20%

*: Classes are defined with a Relative Humidity corresponding to a 9.3 g/kg absolute humidity

The tests will be realized with the following testing conditions:

Technology type

Indoor Rating Temperatures

Outdoor Rating Temperatures

CRAC-A

split unit

Mandatory test point:

CLASS 2


Optional point:

CLASS 1, 3 and 4

Air Entering Temperature:

35°C Dry Bulb

24°C Wet Bulb

If only the internal part is considered in the test (no  condenser), units shall be tested with a fixed condensing temperature:

45°C fixed condensing temperature

 

CRAC-W

Unit

Mandatory test point:

CLASS 2


Optional point:

CLASS 1, 3 and 4

Water Temperature (in/out):

30°C/35°C

CRAH unit

Mandatory test point:

CLASS 2


Optional point:

CLASS 1, 3 and 4

Chilled Water Temperature (in/out):

Conditions below in table 3

 

Hybrid

CRAH/CRAC-A

unit

Mandatory test point:

CLASS 2


Optional point:

CLASS 1, 3 and 4

CRAH part

Chilled Water Temperature (in/out):

Conditions below in table 3

 

CRAC-A part

Air Entering Temperature:

35°C Dry Bulb

24°C Wet Bulb

 

If only the internal part is considered in the test (no condenser), units shall be tested with a fixed condensing temperature:

45°C fixed condensing temperature

 

 

Hybrid

CRAH /CRAC-W

unit

Mandatory test point:

CLASS 2


Optional point:

CLASS 1, 3 and 4

CRAH part

Chilled Water Temperature (in/out):

Conditions below in table 3

 

CRAC-W part

Water Temperature (in/out):

30°C/35°C

 

For CRAH units, the chilled water temperatures (in/out) are the following (table 3):

Class

Mandatory point

(In/Out) temperature

Optional point

(In/Out) temperature

Class 1 - optional

10°/16°

-

Class 2 - mandatory

10°/16°

15°C/21°C

Class 3 -  optional

15°/21°

10°C/16°C

And/or

18°C/24°C

Class 4 - optional

18°/24°

10°C/16°C

And/or

15°C/21°C

 

 

General reference documents


Certification Manual 14th Edition
Reference documents


ITCU Operational Manual-23-2018


ITCU Rating Standard/C/012-2018