You can select a Certification Programme from the list below to retrieve its description (scope of the programme, definitions...)

  See certified products


 
Scope of the programme

Are included in the scope:
- Outdoor units used in Variable Refrigerant Flow systems with the following characteristics:
   o Air or water source,
   o Reversible, heating-only and cooling-only.

Are excluded from the scope:
- VRF systems with data declared and published as combinations.

Heat recovery units are included in the scope but the heat recovery function is not certified.
High ambient systems are included in the scope but tested under standard conditions as specified in RS 6/C/008.

Certify-all: The programme covers all VRF systems with the limitation of cooling capacities of approved independent laboratories. The company participating to this certification programme shall certify all standard production models below the following cooling capacity at standard conditions:

 Capacity (in both modes)
 Max No. of connected indoors
  Ducted horizontal
 Cassette
P <= 20 kW
 4 2
 20 < P <= 50 kW
 4 -
Definitions

Definitions given in prEN 14511-2:2012 and prEN 14511-3:2012 Annex I apply. In addition, the following definitions apply:

System capacity ratio:
Ratio of the total stated cooling (heating) capacity of all operating indoor units to the stated cooling (heating) capacity of the outdoor unit at the rating conditions.
Outdoor cooling capacity (Pc, outdoor)
Total cooling capacity of the outdoor unit measured as the total indoor cooling capacity unit
Outdoor heating capacity (Ph, outdoor)
Heating capacity of the outdoor unit measured as the total indoor heating capacity unit
Outdoor power input (Pe, outdoor)
Effective power input measured on the outdoor unit
Indoor power input (Pe, indoor)
Effective power input measured on the indoor unit
Outdoor energy efficiency ratio (EERoutdoor)
Ratio of the outdoor cooling capacity to the outdoor power input
Outdoor energy efficiency ratio (COPoutdoor )
Ratio of the outdoor heating capacity to the outdoor power input
Testing requirements

Performance testing using the calorimeter room method:
EN 14511 “Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling”.
Performance testing using the air enthalpy method:
EN 14511 “Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling”

EN 12102 “Air conditioners, liquid chilling packages, heat pumps and dehumidifiers with electrically driven compressors for space heating and cooling - Measurement of airborne noise - Determination of the sound power level” with exception of the duct end correction method described in section 6.2.2 of this standard.
Rating requirements

Rating requirements are in accordance with EN 14511.

The corrections of the total cooling capacity or heating capacity due to the power input of fans for indoor units with duct connection described in EN 14511-3 clause 4.1 shall not be carried out.

Performance are defined for a system capacity ratio equals to 100%.
Certified performance items

- Outdoor cooling capacity at standard conditions
- Outdoor Heating capacity at standard conditions
- Outdoor Energy Efficiency Ratio in cooling EER
- Outdoor Coefficient of Performances in heating COP
- A-weighted sound power level outdoor side
General Reference documents


Certification Manual 13th (November 2016)
Reference documents


OM-15-2017


RS-6c008-2016