Home

You can select a Certification Programme from the list below to retrieve its description (scope of the programme, definitions...)

  See certified products


 
Scope of the programme

This Certification Programme applies to air-to-air rooftops and water-to-air rooftops as defined in section III.1 of RS 6/C/007-2017 for Rooftops, rated up to 200 kW in cooling capacity as defined in EN 14511:2013.

Declaring rooftops with 3 or 4 dampers, as described in the section III.1 of RS 6/C/007-2017, is optional.

The following features are not certified:
  • gaz burners,
  • pre-heaters,
  • heaters,
  • additionnal internal coil,
  • heat recovery (plate, wheels, thermodynamic systems),
  • exhaust fans.
The programme is splitted into three sub-programmes:
  • One mandatory sub-programme: Air-to-air units Up to 100 kW
  • Two optional sub-programmes:
                  - Air-to-air units from 100 kW to 200 kW
                  - Water-to-air units up to 200 kW

Minimum and maximum external static pressure requirements are defined in standard EN 14511-3:2013.
Definitions

Rooftop

A rooftop unit is defined by the following features:
  • Air-to-air rooftop: Units covered by ErP regulation (Lot 21) will entry into force on 01/01/2018 and defined as a: Rooftop air conditioner or Rooftop heat pump
  • Water-to-air rooftop: Water-to-air heat pump/air conditioner (defined and covered by the regulation), driven by an electric compressor, of which the evaporateur, compressor and condenser are integrated into a single package.

Features according definitions from ErP regulation:
  • Single packaged unit assembled in factory
  • Common single frame
  • Direct expansion system
  • For Air-to-air unit, the outdoor side heat exchanger (condenser / evaporator) allows heat transfer with 100% outdoor (ambient) air.

Additional features:
  • Designed to operate permanently outdoor
  • The rooftop is designed to permanently handle 100% recycled air with the possibility of mixing partly the fresh air.
  • The outdoor fan from an air-to-air rooftop could be ducted but for the certification tests, the unit must be not ducted.
  • Rooftops could be equiped with 2 / 3 or 4 dampers depending on heat recovery system included or not.

These types of rooftops shall be tested :
  • For the indoor heat exchanger with mixed air equal to 100% extract air and,
  • For the ‘ outdoor ‘ heat exchanger with 100% outdoor air.
  • Other parameters in accordance with the standards EN 14511:2013 and EN 14825:2016.


Basic models groups (BMG)

A Basic Model Groups (BMG) is a list of Rooftops models, part of a common commercial range sharing the same overall dimensions:
  • Height (mm)
  • Width (mm)
  • Length (mm)
with the same function and application (For instance, reversible rooftops and cooling only rooftops are in two separate Basic Model Groups).
with similar components (fans, coils, compressors and motors).


Measured and rated data

a. Definitions in accordance with EN 14511

The definitions of the following items, used in this RS, are given in EN 14511:2013.

  • Cooling Capacity (Pc)
  • Heating Capacity (Ph)
  • Total Power Input (Pe(c) or Pe(h))
  • EER, COP

b. Definitions in accordance with EN 14825

The definitions of the following items, used in this RS, are given in EN 14825:2016.

  • Part Load ratio
  • Part Load conditions
  • SEER
  • SCOP

Testing Requirements

Standard ratings shall be established at the standard rating conditions specified in section V. All standard ratings shall be verified by tests conducted in accordance with the following standards:

1. Performance testing

EN 14511:2013 “Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling”.
Used for:
  • Standard rating points
  • LRcontmin and CcpLRcontmin

EN 14825:2016 "Air conditioners, liquid chilling packages and heat pumps, with electrically driven compressors, for space heating and cooling. Testing and rating at part-load conditions and calculation of seasonal performance”.
Used for:
  • Psb, Pto, Poff, Pck
  • Part Load Conditions in cooling mode
  • Part Load Conditions in heating mode

2. Acoustical testing

EN 12102:2013 “Air conditioners, liquid chilling packages, heat pumps and dehumidifiers with electrically driven compressors for space heating and cooling - Measurement of airbone noise - Determination of the sound power level”.
Rating requirements

Performance ratings claimed by manufacturers shall be verified by tests performed in one of Eurovent Certita Certification Independent Laboratories or in Participant Laboratory (see IV.3).. The following specifications will be used during the tests:

  • Test unit shall be installed with vertical or horizontal airflow in accordance with the manufacturer’s specifications
  • No fresh air shall be used for rating, neither in cooling, nor in heating.
  • The operating conditions shall be used following the Table 1.
  • Allowable deviations from set values are given in EN 14511:2013.
  • Testing shall be carried without mixing damper.
  • The nominal airflow rate and the external static pressure (ESP) given by the manufacturer shall be measured.


Operating conditions for standard rating

  

INDOOR SIDE

OUTDOOR SIDE

  

Air entering °C

Air entering °C

Water °C

  

Dry bulb

Wet bulb

Dry bulb

Wet bulb

In

Out

Cooling

27

19

35

24

30

35

Heating

20

15 max

7

6

20*

 

SOUND**

27

19 (+/-2)

20-35

-

30

35

* For units designated for cooling mode, the water flow rate obtained during the test at standard rating conditions in cooling is used.

** Same airflow and same available pressure as for the thermal test shall be used.

Part-load rating conditions for cooling and heating mode

For each part load conditions, it is possible to vary the air flow of the machine.
Only the damper setting cannot be changed.
Certified characteristics

The following performance characteristics shall be certified and verified by tests:

    a) Total Cooling Capacity
    b) Heating Capacity
    c) EER
    d) COP
    e) Eurovent Energy Efficiency class (cooling and heating)
    f) Condenser water pressure drop (only for water cooled rooftops)
    g) External static pressure (ESP)
    h) Nominal airflow rate (Qv)
    i) A-weighted Sound Power Level outside
    j) A-weighted Sound Power Level in supply duct

From 1st January 2018:

    k) Seasonal Efficiency in Cooling (SEER & ηsc)
    l) Seasonal Efficiency in Heating (SCOP & ηsh)
Energy Efficiency Classification

The purpose of Eurovent Certita Certification Energy Efficiency Classes is to simplify the selection of the best units for each type of Rooftops. The classification is entirely voluntary, not related to any European Directive. The energy efficiency of Rooftops is designated by “Eurovent Certita Certification Class A” or “Eurovent Certita Certification Class B” in catalogues and in the Eurovent Certita Certification Directory of Certified Products. Based on existing units presented to Eurovent Certita Certification the following limits between classes are defined:

ECC Energy Classification of Air-to-air Rooftops - cooling mode

ECC Energy
Efficiency Class

Rooftop units

A

3.00 < EER

B

3.00 ≥ EER > 2.80

C

2.80 ≥ EER > 2.60

D

2.60 ≥ EER > 2.40

E

2.40 ≥ EER

 
ECC Energy Classification of Water-to-air Rooftops - cooling mode

ECC Energy
Efficiency Class

Rooftop units

A

4.40 < EER

B

4.40 ≥ EER > 4.10

C

4.10 ≥ EER > 3.80

D

3.80 ≥ EER > 3.50

E

3.50 ≥ EER

 
ECC Energy Classification of Air-to-air Rooftops - heating mode

ECC Energy
Efficiency Class

Rooftop units

A

3.40 < COP

B

3.40 ≥ COP > 3.20

C

3.20 ≥ COP > 3.00

D

3.00 ≥ COP > 2.60

E

2.60 ≥ COP

 
ECC Energy Classification of Water-to-air Rooftops - heating mode

ECC Energy
Efficiency Class

Rooftop units

A

4.70 < COP

B

4.70 ≥ COP > 4.40

C

4.40 ≥ COP > 4.10

D

4.10 ≥ COP > 3.80

E

3.80 ≥ COP

1
Symbols used in the directory

 Pc

Cooling Capacity

 Pe(c)

Power input in Cooling mode 

 EER

Energy Efficiency Ratio 

 Ph

Heating Capacity 

 Pe(h)

Power input in heating Mode

 COP

Coefficient of Performance 

 MPS

 Main Power Supply

 Lwo Env

 A-Weighted sound power level outside

 Lwi Duct

 A-Weighted sound power level in supply duct

Classification of equipment

Programme

Heat rejection

System

Operation

Rooftop

RT

Air source

A

Packaged

P

Cooling Only

C

General Reference documents


Certification Manual 13th (November 2016)
Reference documents


OM-13-2017


RS-6C007-2017