Home

You can select a Certification Programme from the list below to retrieve its description (scope of the programme, definitions...)

  See certified products


 
Scope of the programme

This certification programme is divided into four sub-programmes:
- AC1: comfort units with cooling capacity up to 12 kW
- AC2: comfort units with cooling capacity from 12 to 45 kW
- AC3: comfort units with cooling capacity from 45 to 100 kW
- CC: Close Control Air Conditioners up to 100 kW

This programme applies to factory-made units intended to produce cooled air for comfort air conditioning (AC1, AC2, AC3) or close control air conditioning (CC). It also applies to units intended for both cooling and heating by reversing the cycle.

Multi-split with data declared and published as combination of outdoor and indoor units with 2 indoor units only: each unit individually connected to the outdoor unit and with an expansion device inside the outdoor unit. The 2 indoor units have to be of the same mounting type. For AC1 connection capacity ratio must be 1 ± 0.05.

Participating Companies must certify all production models within the scope of the programme they enter. However concerning multi-split air conditioners only systems with two indoor units are included.

The complete description of close control air conditioners (CC) is detailed in a specific web page (go back to the choice list)
Definitions

Air conditioner
A device capable of cooling or heating, or both, indoor air, using a vapour compression cycle driven by an electric compressor, including air conditioners that provide additional functionalities such as dehumidification, air purification, ventilation or supplemental air heating by means of electric resistance heating, as well as appliances that may use water (either condensate water that is formed on the evaporator side or externally added water) for evaporation on the condenser, provided that the device is also able to function without the use of additional water, using air only.

Heat pump
Encased assembly or assemblies designed as a unit, using a vapour compression cycle driven by an electric compressor, to provide delivery of heat.

Comfort air conditioner or heat pump
Air conditioner or heat pump to satisfy the comfort requirements of the occupants of the air conditioned room.

Packaged unit
factory assembly of components of refrigeration system fixed on a common mounting to form a discrete unit.

Single split unit
Factory assembly of components of refrigeration system fixed on two mountings to form a discrete matched functional unit.

Single-duct air conditioner
Air conditioner in which, during cooling or heating, the condenser (or evaporator) intake air is introduced from the space containing the unit and discharged outside this space.

Double-duct air conditioner
Air conditioner in which, during cooling or heating, the condenser (or evaporator) intake air is introduced from the outdoor environment to the unit by a duct and rejected to the outdoor environment by a second duct, and which is placed wholly inside the space to be conditioned, near a wall.

Total cooling capacity, Pc [kW]
Heat removed by the air conditioner from air per period of time.

Heating capacity, Ph [kW]
Heat supplied by the reverse cycle air conditioner to air per period of time.

Effective power input, Pe [kW]
Average electrical power input to the unit, within the defined interval of time, obtained from:
- the power input for operation of the compressor and any power input for defrosting
- the power input of all control and safety devices of the unit
- the proportional power input of the conveying devices (e.g., fans, pumps) for ensuring the transport of the heat transfer media inside the air conditioner.

A-weighted sound power level, Lw [db(A)]
A single figure on a specific scale which can be related to the subjective assessment of the loudness of a noise.

Air Conditioners AC1:

Table 1: Reference design temperatures

 

Design Temperature [°C]

Bivalent temperature [°C]

Operating limit Temperature [°C]

Outdoor

Indoor

Cooling

35 (24)

27 (19)

n.a

n.a

Heating / Average

-10

20 (15 max)

+2 or lower

-7 or lower

Heating / Warmer

+2(1)

20 (15 max)

+7 or lower

+2 or lower

Heating / Colder

-22

20 (15 max)

-7 or lower

-15 or lower

Testing requirements

Standard ratings shall be established at the standard rating conditions specified in the section "Rating requirements" of the Rating Standards. All standard ratings shall be verified by tests conducted in accordance with the following standards:

 Performance testing:

 Test method:

EN 14511-3:2013 "Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling- Part 3: Test methods"

 Test conditions: (only for AC1)

EN 14825:2013 "Air conditioners, liquid chilling packages and heat pumps, with electrically driven compressors, for space heating and cooling. Testing and rating at part load conditions and calculation of seasonal performance"

 Acoustic testing:

 EN 12102:2013 "Air conditioners, liquid chilling packages, heat pumps and dehumidifiers with electrically driven compressors for space heating and cooling - Measurement of airbone noise - Determination of the sound power level" with exception of the duct end correction method described in section 6.2.2 of this standard.

 Specifications concerning temperature conditions and installation of units for acoustical testing are defined in the Document RS 6/C/006.

Rating requirements

Air Conditioners AC1

Reference design temperatures and operational hours used in the calculation of SEER and SCOP and the annual power consumption must be in accordance with Table 2.

Table 2: Operational hours per type of appliance per functional mode
 

 

Mode

Season

On mode [h]

Thermostat off mode [h]

Standby mode [h]

Off mode [h]

Crankcase heater mode [h]

Cooling HCE

heating HHE

HTO

HSB

HOFF

HCK

Cooling only

Cooling

-

350

221

2142

5088

7760

Reversible

Cooling

-

350

221

2142

0

2672

Heating

Average

1400

179

0

0

179

Warmer

1400

755

0

0

755

Colder

2100

131

0

0

131

Heating only

Heating

Average

1400

179

0

3672

3851

Warmer

1400

755

0

4345

4476

Colder

2100

131

0

2189

2944


It has to be noted that for the heating application declaration at warmer and colder climate are optional.

Heating mode +7°C

For capacity test at +7°C the following standard rating conditions (Table 3) shall be used:

Table 3: Operating conditions for standard rating

 

INDOOR UNIT

OUTDOOR UNIT

Air entering [°C]

Air entering [°C]

Dry bulb

Wet bulb

Dry bulb

Wet bulb

Comfort Air Conditioner - Heating mode

20

15 max

7

6


Part Load rating conditions

For part load test the following standard rating conditions (Table 4 and Table 5)

shall be used.

Table 4: Part load conditions for reference SEER and reference SEERon calculation of air-to-air units

 

Targeted

Part-load

Ratio [%]

Outdoor heat exchanger

Indoor heat exchanger

Outdoor air dry bulb temperature [°C]

Indoor air dry bulb (wet bulb) temperatures [°C]

A*

100

35

27(19)

B

74

30

27(19)

C

47

25

27(19)

D

21

20

27(19)

 

* Part-load condition A for cooling mode is coincident with the standard rating condition defined in EN 14511-2:2013

 

Table 5: Part-load conditions for reference SCOP reference SCOPon and reference SCOPnet calculation of air-to-air units

 

Targeted Part load ratio [%]

Outdoor heat exchanger

Indoor heat exchanger

 

Colder Climate

Average climate

Warmer climate

Air dry (wet) bulb T [°C]

Inlet air dry bulb T [°C]

Gb

(-15-16)/(Tdesignh -16)

82

 

 

-15

20

Ac

(-7-16)/(Tdesignh -16)

61

88

 

-7(-8)

20

B

(+2-16)/(Tdesignh -16)

37

54

100

2(1)

20

C

(+7-16)/(Tdesignh -16)

24

35

64

7(6)

20

D

(+12-16)/(Tdesignh -16)

11

15

29

12(11)

20

Ed

(TOL-16)/(Tdesignh-16)

 

 

 

TOLa

20

F

(Tbivalent-16)/(Tdesignh-16)

 

 

 

Tbivalenta

20

a For Tbivalent and TOL higher or equal to -7°C the wet bulb temperature equals the dry bulb temperature minus 1°C.  For Tbivalent and TOL below -7°C, the wet bulb temperature is not defined.

b Applicable onlyfor rating at colder climate, if TOL < -20ºC.

c Not requested for rating at warmer climate.

d If TOL<Tdesignh, then the test is performed with an outdoor air dry bulb temperature of Tdesignh (Tdesignh = -10°C for the avg climate)


Air Conditioners AC2 and AC3

Standard rating conditions are used.The ambient temperature surrounding units or parts with duct connection on the air inlet and outlet sides are set between 15°C and 30°C.


  Outdoor unit Indoor unit
Air entering [°C] Water [°C] ** Air entering [°C]
Dry bulb Wet bulb In Out *** Dry bulb Wet bulb
Comfort air conditioner
cooling
35 24 30 35 27 19
Comfort air conditioner
heating
7 6 5**** - 20 15 max

* This temperature applies to such equipment where the wet bulb temperature affects the heat exchange in the outdoor side (unit using latent heat of water as all or portion of the heat source or sink for the outdoor heat exchanger).

** The water flow rate for the heating test shall be the same as used for the cooling test.

*** If the manufacturers' water flow rate is the constant, it is allowable for the water out temperature to differ from the figure shown.

**** Or manufacturers recommended minimum temperature whichever is the higher.

 

Certified characteristics

The following characteristics of comfort air conditioners are verified by tests :

 Air Conditioners AC1

In Cooling mode:

  • Design load Cooling (capacity)
  • Seasonal Energy Efficiency Ratio
  • Seasonal Energy Efficiency Ratio Class
  • Annual electricity consumption for cooling
  • Energy Efficiency Ratio at T=+35°C
  • Power consumption in standby mode

 In Heating mode (for reverse cycle units):

  • Design load Heating (capacity)
  • Seasonal coefficient of performance for the average climate
  • Seasonal coefficient of performance Class for the average climate
  • Annual electricity consumption for heating
  • Bivalent Temperature
  • Heating capacity and Coefficient of Performance at bivalent temperature condition
  • Heating Capacity and Coefficient Of Performance at +7°C (nominal)
  • Power input in auxiliary modes

 Sound:

  • A-weighted sound power indoor side (non ducted units)
  • A-weighted sound power outdoor side (non ducted units)
  • A-weighted sound power radiated from the duct (ducted units)

 Air Conditioners AC2 and AC3:

In Cooling mode:

  • Total cooling capacity
  • Energy efficiency ratio

In Heating mode (for reverse cycle units):

  • Heating capacity
  • Coefficient of performance (Heating mode)

Sound:

  • A-weighted sound power indoor side (non ducted units)
  • A-weighted sound power outdoor side (non ducted units)
  • A-weighted sound power radiated from the duct (ducted units)
 

Energy labelling of air conditioners up to 12 kW

Commission Delegated Regulation (EU) No 626/2011 of 4 May 2011 supplementing Directive 2010/30/EU of the European Parliament and of the Council with regard to energy labelling of air conditioners makes it obligatory for all concerned units to have labelling when they are presented for sale in shops or department stores. Although not mandatory it was decided to include labelling in the present Directory of Certified Products which will give much more dissemination to this action.

All air conditioners with a cooling capacity under 12 kW (AC1) are concerned.

Directive defines for each type of product the energy class going from A (more efficient) to G (less efficient). The energy efficiency class is determined in accordance with the following tables:

       Energy Classification for Conditioners except double ducts and single ducts

 


Energy Efficiency Class

SEER

SCOP

A+++

SEER ≥ 8.50

SCOP ≥ 5.10

A++

6.10 ≤ SEER < 8.50

4.60 ≤ SCOP < 5.10

A+

5.60 ≤ SEER < 6.10

4.00 ≤SCOP < 4.60

A

5.10 ≤ SEER < 5.60

3.40 ≤ SCOP < 4.00

B

4.60 ≤ SEER < 5.10

3.10 ≤ SCOP < 3.40

C

4.10 ≤ SEER < 4.60

2.80 ≤ SCOP < 3.10

D

3.60 ≤ SEER < 4.10

2.50 ≤ SCOP < 2.80

E

3.10 ≤ SEER < 3.60

2.20 ≤ SCOP < 2.50

F

2.60 ≤ SEER < 3.10

1.90 ≤ SCOP < 2.20

G

SEER < 2.60

SCOP < 1.90

1

Symbols used in the directory

Pc Total cooling capacity kW
Ph Total heating capacity kW
Pe Effective power input kW
Lw A-weighted sound power level dB(A)
Lw env A-weighted sound power level around the unit              dB(A)
Lw in duct A-weighted sound power level in the duct dB(A)
MPS Main Power Supply  
SEER

Seasonal Energy Efficiency Ratio

 
SCOP

Seasonal Coefficient of Performance

 
Qhe / Qce Annual electricity consumption for heating or cooling kWh
Pdesign Design Load       kW
Tbiv Bivalent Temperature   °C
TOL Operating Limit Temperature    °C
Poff Power consumption in off mode W
Psb Power consumption in standby mode cooling W
Pto Power consumption in thermostat off mode W
Pck Power consumption of the crankcase heater W
Classification of equipment

Programme Code
Heat rejection Code System Code Operation Code Mounting* Code

Comfort Air Conditioners
up to 12 kW

 AC1

Air cooled ASplit S Cooling only
C High wall
W
Floor mounted
L
Cassette C
Comfort Air Conditioners
from 12 up to 45 kW
 AC2 Multisplit M
Ceiling suspended S
Water cooled
W Reverse cycle R
Comfort Air Conditioners
from 45 up to 100 kW
 AC3 Built-in horizontal B
Packaged P
Close Control Air Conditioners up to 100 kW
 CC Built-in vertical
V
Window Wi

* Other applications according to specific information

General Reference documents


Certification Manual 13th (November 2016)
Reference documents


OM-1-2017



RS 6C001A-2016



RS 6C001-2016



RS-6C006-2015